ISE, Inc. .

West Temperature Control Specifications

Series 4700, 6700 High/Low Limit Controls

 

FM Approved Limit with Push Button Reset.

Logs High, Low Temperature & Time in Excess of Setpoint.

Maximum Number of Inputs: (1) analog, (1) TTL Logic for Reset (optional).

Input Sample Rate: Four times/second.

Input Resolution: Four times better than display resolution.

DC Linear Input Scaling: User programmable scale range minimum: -1999 to 9999; Scale range maximum: -1999 to 9999; Decimal point user programmable; Minimum span 1 display LSD.

Outputs: Up to three available.

Relay Outputs: SPDT 2A resistive 240VAC maximum > 500,000 operations at rated current/voltage.

DC Linear Output: Eight bits in 250mS; 10 bits in 1 second

Maximum Number of Alarms: Two “soft” alarms plus loop alarm which can utilize up to two outputs.

Communications: RS485 Serial asynchronous with user selectable address 1-32; Baud rate selectable from 9600, 4800, 2400, 1200 baud.

Operating Conditions: 0 to 55 degrees C; 20-95% RH non-condensing; 90-264VAC or optional 20-50VAC/22-65VDC supply voltage.

Thermocouple Source Resistance: 1000 ohm maximum

RTD Lead Resistance: 50 ohm maximum (balanced)

Accuracy: +/- 0.25% of span +/- 1 LSD

Click here for our complete line of temperature controls

[HRule Image]

To build a Part Number fill in the selections below.

MODEL

4701 1/4 DIN Limit Control (programable as High or Low Limit)

6701 1/16 DIN Limit Control (programable as High or Low Limit)

 

INPUT TYPE

1 3 Wire RTD or DC Millivolts
2 Thermocouple
3 DC Milliamps
4 DC Volts


Output #1

1 Relay


Output #2

0 None
1* Relay


Output #3
0 None
1* Relay
3* DC 0-10VDC Recorder (retransmit) output only
4* DC 0-20mA Recorder (retransmit) output only
5* DC 0-5VDC Recorder (retransmit) output only
7* DC 4-20mA Recorder (retransmit) output only

Options
00 None
10* RS485 Serial Communications (Cannot use with option 30)
02* 24VAC/24VDC Power Supply (instead of 90-264VAC)
30* Remote Reset

* Items marked are optional and are extra cost. Most features are easily upgradeable in the field via plug in option boards.

[HRule Image]

Output types and proper uses:

Relay: Form C contact output suitable for any voltage up to 2 Amps/240 VAC; Use to drive mechanical contactors, relays, mercury contactors Din-A-Mites with AC Voltage inputs.

Retransmit Outputs: Supply other equipment with a linear signal proportional to the input or setpoint value.

Outputs #2 & #3 (Relay ) can be utilized as an alarm output (high process, deviation high, deviation low, band)

So that ISE can totally configure your instrument for your application we need the following information:

1) Model number
2) Use for each output
3) General application description (i.e. Oven Protection)

We will assist in the selection of the proper control and model number for your application. Fill in information at the bottom of this page to receive a quotation, literature or other information.

[HRule Image]

Below are some links to our most popular web pages (click on the graphic to follow the link). For a complete listing click Products.

 

HOME

PRODUCTS

 

SEARCH

FEEDBACK

Track a shipment from ISE     Transit times for UPS Ground from ISE 

[HRule Image]

Information Request Form

Select the items that apply, and then let us know how to contact you.

Send product literature
Send company literature
Have a salesperson or application engineer contact me
Send Quote

Which product(s) do you have an interest?

West 4701 West 6701

Other:

To Receive a Quotation Enter Model Number and/or Describe your Application

Model:

Application Description:

 Name: 
     Title: 
   Company: 
Address: 
	 
	 
City:   State:
Zip/Postal:   Country: 
    E-mail: 
     Phone: 
       Fax: 

 

Last modified: December 31, 2007

 

   

Headquarters
10100 Royalton Rd.,  Cleveland, OH  44133  USA
Phone: (440) 237-3200  Fax: (440) 237-1744
Email ISE Cleveland
 
Toledo Area Office
417 Tomahawk Drive,  Maumee, Oh 43537
Phone: 419-893-3330 - FAX: 419-893-2151
Email ISE Toledo  
 

ISE, Inc. Privacy Policy

Click for Cleveland, Ohio Forecast Copyright © 2008 ISE, Inc.  All rights reserved.